AMT B1x-SAxTE for active energy measuring, 1-rate, up to 100 A

Three-phase static electricity meters AMT B1x-SxxTE are determined for single-rate active energy measurement in direct and indirect connection, displaying results on mechanical register with stepping motor. In the case of CT (current transformer) operated meters (x/5A) it is necessary value of register to multiply by the current transformer ratio. The test pulses indicated by red LED are proportional to the consumed energy. Measurement „using an unidirectional mechanical register“ provides positive energy measurement even if the reverse energy flow.

Properties

  • Passive transmitting pulse SO output for remote transmission;
  • Indication of voltage presence and reverse energy flow;
  • Resistant to external influence;
  • Welded case on a customer requirement;
  • Compliance with IEC/EN 62052-11, IEC/EN 62053-21; EN 50470-1, EN 50470-3 and with requirements of European Parliament and EC Directive 2014/32/EU (MID);
  • It is supplied initially verificated for billing measurement.

Technical data

Precision class A or B (according to MID),
2 or 1 (accord. to EN 62053-21)
Reference voltage [V] 3 x 220/380,
3 x 230/400, 3 x 240/415,
3 x 120/208, 3 x 57,7/100 (-30,+15%)
Reference frequency [Hz] 50 or 60
Reference current Iref [A]
direct connection
5 and 10
Nominal current In [A]
indirect connection

Transient current Itr [A]
direct/indirect connection
0,5 and 1 / 0,25
Starting current Ist [A]
direct/indirect connection
≤ 0,02 a 0,04 / 0,01
Minimal current Imin [A]
direct/indirect connection
0,25 a 0,5 / 0,05
Maximal current Imax [A]
direct/indirect connection
100/10
Power consumption - voltage circuit  [VA/W] ≤ 7,5/0,4
Power consumption - current circuit [VA] ≤ 0,1
Impulse constant for test output kTO  [imp/kWh] 1600
Impulse constant for impulse output kSO [imp/kWh] 1600
Transistor output SO 24 V / 30 mA
Operating temperature  -40 °C up to +70 °C
Mean temperature coefficient [%/K] ≤ 0,02
Terminals current; voltage ; auxiliary [mm] ø 8 ; ø 3 ; ø 3 
Degree of protection IP54
Fixing holes distance - w x h [mm] 150 x 215-230
Meter dimensions - w x h/h´x d [mm] 177 x 187/251 x 60
Weight [kg] ≤ 1,30