Portable test equipment PTE

The Portable Test Equipment consists of an integrated current and voltage source and electronic reference standard of accuracy class 0,05 % or 0,02%. Device is available in three-phase version PTE 2300 or single phase version PTE 2100.

Properties

  • Laboratory and on-site meter measurements
  • Easy evaluation of meters under precise load conditions, using the built-in compact current and voltage source
  • Testing of meters with closed I-P links
  • Automatic operation with predefined load points without the need for an external computer
  • Each source channel can be programmed with user defined harmonic content or standardized signal test shapes
  • Each source channel can be modulated with programmable Ripple control telegram
  • Independent generation of single or three-phase loading conditions for testing, calibration and verification of meters
  • Active, reactive and apparent energy measurement for three phase, 3 or 4-wire, systems with integrated error calculator and pulse output
  • Capable to test the ratio and burden of CT/PT

Technical data

Power Source (built-in/specification per phase)
Voltage
Range 3 ... 300 V (phase to neutral)
Output power 30 VA
Accuracy 0,015 % (PTE 2x00E); 0,035 % (PTE 2x00A)
Distortion factor < 0,3 %
Resolution 0,01 V
Stability < 0,005 % (within 60 min period @ time base 150 s)
Current  
Range 1 mA ... 120 A
Output power 60 VA max @ 60-120 A / 1 V max @ 0-60 A (120 A output)
42 VA max @ 12 A / 5 V max (12 A output)
Accuracy *1 0,015 % (PTE 2x00E), 0,035 % (PTE 2x00A) 
Distortion factor < 0,3 %
Resolution min. 0,1 mA
Stability < 0,005 % (within 60 min period @ time base 150 s
Phase Angle  
Range 0° ... 360°
Resolution < 0,001° (45 … 100 Hz)
Harmonics  
Fundamental  Frequency Range 40 Hz ... 70 Hz
Bandwidth 30 … 2200 Hz
Phase Shift 0° … 360°
Max. amplitude 50 (2nd ... 6th harmonics); 15 %  (7th ... 40th harmonics)
Ripple Control  
Frequency Range 100 ... 1600 Hz
Modulation 0 … 15 %
Channels Selection any combination of Voltage and Current channels
General Specifications  
Oper. Temperature -10 ... +50 °C
Storage Temperature -20 ... +60 °C
Operating Humidity < 85 % at Ta<21°C; < 95 % at Ta<25°C (30 days / year spread)
Power Consumption approx. 550 VA
Power Supply 100 VAC ... 550 VAC
Degree of Protection IP-67 (closed case)
Safety Requirements Isolation protection: EN 61010-1:2001
Measurement category: 300 V CAT III, 600 V CAT IV
Dimensions (W x D x H)
470 x 370 x 180 mm (device)
Weight (approx.) 16,5 kg (device) / 5 kg (accessories)

*1 in range 1 mA ... 30 mA related to 30 mA