AMS B1x-SAx for active energy measuring, with mechanical register

Single-phase static electricity meters AMS B1x-SAx are determined for direct and indirect measurement of active energy displaying value on mechanical register with stepping motor. In the case of CT (current transformer) operated meters (x/5A) it is necessary value of register to multiply by the current transformer ratio. The test pulses indicated by red LED are proportional to the consumed energy. Measurement „using an unidirectional mechanical register“ provides positive energy measurement even if the reverse energy flow.

Properties

  • The meters can be mounted on the DIN rail (the clips only on request);
  • Removable and adjustable upper hinge is included in the package;
  • Passive transmitting pulse SO output for remote transmission;
  • Indication of voltage presence and reverse energy flow;
  • Resistant to external influence;
  • Complies with IEC/EN 62052-11, IEC/EN 62053-21;
    EN 50470-1, EN 50470-3 and with requirements of European Parliament and EC Directive 2014/32/EU (MID);
  • It is supplied initially verificated for billing measurement.

Technical data

Precision class A or B (according to MID),
2 or 1 (accord. to EN 62053-21)
Reference voltage [V] 120, 220, 230, 240
(-30,+15%)
Nominal frequency [Hz] 50 or 60
Reference current Iref [A]
direct connection
5 and 10 
Nominal current In [A]
indirect connection

Transient current Itr [A]
direct/indirect connection
0,5 and 1 / 0,25
Starting current Ist [A]
≤ 0,02 and 0,04 / 0,01
Minimal current Imin [A]
direct/indirect connection
0,25 a 0,5 / 0,05
Maximal current Imax [A]
direct/indirect connection
40, 60, 80, 100 / 6; 7,5; 10
Power consumption - Voltage circuit [VA/W] ≤ 7,5/0,4 
Power consumption - Current circuit [VA] ≤ 0,1
Impulse constant for test output kTO [imp/kWh] 1 – 10 000, normally 6 400
Impulse constant for impulse output kSO [imp/kWh] 1 – 10 000, normally 6 400
Transistor output SO 24 V / 30 mA
Operating temperature -40 °C up to +70 °C
Mean temperature coefficient [%/K] ≤ 0,04
Terminals current ; voltage ; auxiliary  [mm] ø 8 ; ø 3 ; ø 3 
Degree of protection IP54 
Fixing holes distance - w x h [mm]  104 - 112 x 115 - 155
Meter dimensions - w x h/h´x d [mm]  130 x 129/190 x 60
Weight [kg] ≤ 0,6